GXR-2000SI

GXR-2000SI

GXR-2000SI Specification
General
Model SMAP GXR-2000SI UPS
Topology True on-line double conversion
Configuration Rack/Tower
Catalogue Series GXR, 2U Rack/Tower UPS
Rating (VA/Watts) 2000/1800
Dimension (W x D x H, mm) 438 x 630 x 88
Dimension (W x D x H, inches) 17.2 x 24.8 x 3.5
Net Weight 26.9 kg
Efficiency 92%; ECO mode: 98%
Transfer Time Zero
Waveform Pure sine wave
Electrical Input
Input Phase Single phase with ground (2 wires + ground)
Input Connection (1) IEC60320-C20, 16A IEC320-16A C20
Voltage Range 110VAC ~ 300VAC ±5%
Frequency Range 40Hz ~ 70Hz auto sensing
Input Power Factor ≥0.99
Electrical Output
Output Phase Single phase with ground (2 wires + ground)
Output Receptacle (8) IEC60320-C13, 10A IEC320-10A C13
Output Voltage 220VAC (Default: configurable to 200/208/220/230/240VAC)
Voltage Regulation ± 1%
Synchronized Frequency Range 50/60 Hz ± 0.1 Hz
Output Power Factor 0.9
Current Crest Ratio 3:1
Harmonic Distortion (THDu) ≤2% THD (Linear Load)
Overload capability 110% continuous; 110%~130% with 5 min
Battery
Battery Sealed Lead Acid Maintenance Free battery
Battery Voltage 72VDC
Typical Recharge Time Depends on the capacity of the external battery bank
Indicators, Communications & Management
Rotatable LCD Panel UPS status, load level, battery level, input/output voltage, discharge remaining time, and fault conditions
Audio and Visible Alarms Battery mode, low battery, overload, fault
Communications USB / RS-232, SNMP RJ-45 network, dry contact, intelligent slot
EPO Yes
Optional Accessories SNMP Network management card, Modbus card, Dry contact card, Isolation transformer, Maintenance bypass switch, ATS 16 switch, External battery pack
Support Software Windows family, Linux, Unix, Mac, Hyper-V, VMware, etc.
Environmental & Standards
Operating Conditions 0 ~ 95% RH @0 ~ 40°C (non-condensing)
Audible Noise < 48 dB at 1 meter
IP Rating IP20 (other option)
Safety & Standards IEC/EN 62040-1/2/3, CE