| General |
| Model |
SMAP GXR-2000SI UPS |
| Topology |
True on-line double conversion |
| Configuration |
Rack/Tower |
| Catalogue Series |
GXR, 2U Rack/Tower UPS |
| Rating (VA/Watts) |
2000/1800 |
| Dimension (W x D x H, mm) |
438 x 630 x 88 |
| Dimension (W x D x H, inches) |
17.2 x 24.8 x 3.5 |
| Net Weight |
26.9 kg |
| Efficiency |
92%; ECO mode: 98% |
| Transfer Time |
Zero |
| Waveform |
Pure sine wave |
| Electrical Input |
| Input Phase |
Single phase with ground (2 wires + ground) |
| Input Connection |
(1) IEC60320-C20, 16A |
 |
| Voltage Range |
110VAC ~ 300VAC ±5% |
| Frequency Range |
40Hz ~ 70Hz auto sensing |
| Input Power Factor |
≥0.99 |
| Electrical Output |
| Output Phase |
Single phase with ground (2 wires + ground) |
| Output Receptacle |
(8) IEC60320-C13, 10A |
 |
| Output Voltage |
220VAC (Default: configurable to 200/208/220/230/240VAC) |
| Voltage Regulation |
± 1% |
| Synchronized Frequency Range |
50/60 Hz ± 0.1 Hz |
| Output Power Factor |
0.9 |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion (THDu) |
≤2% THD (Linear Load) |
| Overload capability |
110% continuous; 110%~130% with 5 min |
| Battery |
| Battery |
Sealed Lead Acid Maintenance Free battery |
| Battery Voltage |
72VDC |
| Typical Recharge Time |
Depends on the capacity of the external battery bank |
| Indicators, Communications & Management |
| Rotatable LCD Panel |
UPS status, load level, battery level, input/output voltage, discharge remaining time, and fault conditions |
| Audio and Visible Alarms |
Battery mode, low battery, overload, fault |
| Communications |
USB / RS-232, SNMP RJ-45 network, dry contact, intelligent slot |
| EPO |
Yes |
| Optional Accessories |
SNMP Network management card, Modbus card, Dry contact card, Isolation transformer, Maintenance bypass switch, ATS 16 switch, External battery pack |
| Support Software |
Windows family, Linux, Unix, Mac, Hyper-V, VMware, etc. |
| Environmental & Standards |
| Operating Conditions |
0 ~ 95% RH @0 ~ 40°C (non-condensing) |
| Audible Noise |
< 48 dB at 1 meter |
| IP Rating |
IP20 (other option) |
| Safety & Standards |
IEC/EN 62040-1/2/3, CE |