GXR-1000S Specification
| General | ||
| Model | SMAP GXR-1000S UPS — 2U Rack Mount | |
| Topology | True on-line double conversion | |
| Configuration | Rack/Tower | |
| Catalog Series | GXR-1000S | |
| Rating (VA/Watts) | 1000 / 900 | |
| Dimensions (W x D x H, mm) | 438 x 410 x 88 | |
| Dimensions (W x D x H, inches) | 17.2 x 16.1 x 3.5 | |
| Net Weight | 14.2 kg | |
| Efficiency | 90% | |
| Transfer Time | Zero | |
| Waveform | Pure sine wave | |
| Electrical Input | ||
| Input Phase | Single phase with ground (2 wires + ground) | |
| Connection | (1) IEC60320 C14, 10A | |
| Voltage Range | 110 ~ 300 VAC ± 3% | |
| Input Frequency | 50/60 Hz ± 3 Hz (auto sensing) | |
| Frequency Range | 40 ~ 70 Hz | |
| Input Power Factor | > 0.99 | |
| Electrical Output | ||
| Output Phase | Single phase with ground (2 wires + ground) | |
| Output Receptacles | (8) IEC60320 C13, 10A | |
| Output Voltage | 220 VAC default; configurable to 208/230/240 VAC | |
| Voltage Regulation | ± 1% | |
| Synchronized Frequency Range | 50/60 Hz ± 3 Hz | |
| Frequency Regulation | 50/60 Hz ± 0.1 Hz | |
| Output Power Factor | 0.9 | |
| Current Crest Ratio | 3:1 | |
| Harmonic Distortion (THDU) | ≤ 2% (linear load) | |
| Battery | ||
| Battery Type | Valve regulated lead-acid, maintenance-free | |
| Battery Voltage | 36 VDC hot-swap battery pack design | |
| Typical Recharge Time | 3 hours to recover to 90% capacity | |
| Battery Design Life | 3 ~ 5 years | |
| Indicators, Communications & Management | ||
| LCD Panel | UPS status, load level, battery level, input/output voltage, discharge remaining time, and fault conditions | |
| Audio and Visible Alarms | Battery mode, low battery, overload, fault | |
| Communications | USB / RS-232, SNMP RJ-45 network, intelligent slot | |
| EPO | Yes | |
| Optional Accessories | Dry contact, Modbus, ATS-16, maintenance bypass switch | |
| Management Software | Supports Windows, Linux, Unix, and Mac | |
| Environmental & Standards | ||
| Operating Conditions | 0 ~ 95% RH @ 0 ~ 40°C (non-condensing) | |
| Operating Altitude | < 2,000 m | |
| Audible Noise | < 48 dB at 1 meter | |
| Safety & Standards | IEC/EN 62040-1/2/3, CE | |